protocol.md 14.8 KB

MODBUS Application Protocol SPecification V1.1b3

Introduction

MODBUS is an application layer messaging protocol for client/server communication between devices connected on different types of buses or networks.

It is currently implemented using:

  • TCP/IP over Ethernet. See MODBUS Messaging Implementation Guide V1.0a.
  • Asynchronous serial transmission over a variety of media (wire : EIA/TIA -232-E, EIA-422, EIA/TIA-485-A; fiber, radio, etc.)
  • MODBUS PLUS, a high speed token passing network.

Abbreviations

Abbreviation Description
ADU Application Data Unit
HDLC High Level Data Link Control
HMI Human Machine Interface
IETF Internet Engineering Task Force
I/O Input / Output
IP Internet Protocol
MAC Media Access Control
MB MODBUS Protocol
MBAP MODBUS Application Protocol
PDU Protocol Data Unit
PLC Programmable Logic Controller
TCP Transmission Control Protocol

Context

The MODBUS protocol allows an easy communication within all types of network architectures. Every type of devices (PLC, HMI, Control Panel, Driver, Motion control, I/O Device...) can use MODBUS protocol to initiate a remote operation. The same communication can be done as well on serial line as on Ethernet TCP/IP networks. Gateways allow a communication between several types of buses or network using the MODBUS protocol.

General Description

Protocol description

The MODBUS protocol defines a simple protocol data unit (PDU) independent of the underlying communication layers. The mapping of MODBUS protocol on specific buses or network ccan introduce some additional fields on the Application Data Unit (ADU).

                                        ADU
<-------------------------------------------------------------------------------->
+--------------------+  +---------------+ +---------------------+  +-------------+
| Additional address |  | Function code | |         Data        |  | Error check |
+--------------------+  +---------------+ +---------------------+  +-------------+
                        <--------------------------------------->
                                        PDU
General MODBUS frame

The MODBUS application data unit is built by the client that initiates a MODBUS transaction. The function indicates to the server what kind of action to perform. The MODBUS application protocol establishes the format of a request initiated by a client. The function code field of a MODBUS data unit is coded in one byte. Valid codes are in the range of 1..255 decimal ( where the range 128 - 255 is reserved and used for exception responses.) When a message is sent from a Client to a Server device the function code field tells the server what kind of action to perform. Function code "0" is not valid.

Sub function codes are added to some function codes to define multiple actions. The data field of messages sent from a client to server devices contains additional information that the server uses to take the action defined by the function code. This can include items like discrete and register addresses, the quantity of items to be handled, ad the count of actual data bytes in the field. The data field may be non-existent (of zero-length) in certain kinds of requests, in this case the server does not require any additional information. The function code alone specifies the action.

If no error occurs related to the MODBUS function requested in a properly received MODBUS ADU the data field of a response from a server to a client contains the data requested. If an error related to the MODBUS function requested occurs, the field contains an exception code that the server application can use to determine the next action to be taken. For example a client can read the ON / OFF states of a group of discrete outputs or inputs or it can read/write the data contents of a group of registers. When the server responds to the client, it uses the function code field to indicate either a normal (error-free) response or that some kind of error occurred (called an exception response). For a normal response, the server simply echoes to the request the original function code.

For an exception response, the server returns a code that is equivalent to the original function code from the request PDU with its most significant bit set to logic 1.

The size of the MODBUS PDU is limited by the size constraint inherited from the first MODBUS implementation on Serial Line network (max. RS485 ADU = 256 bytes).

Therefore:
MODBUS PDU for serial line communication = 256 - Server address (1 byte) - CRC (2 bytes) = 253 bytes.

Consequently:
RS232 / RS485 ADU = 253 bytes + Server address (1 byte) + CRC (2 bytes) = 256 bytes. TCP MODBUS ADU = 253 bytes + MBAP (7 bytes) = 260 bytes. The MODBUS protocol defines three PDUs. They are :

Full name PDU Definition Description
MODBUS Request PDU mb_req_pdu {function_code, request_data} function_code = [1 byte] MODBUS function code
request_data = [n bytes] This field is function code dependent and usually contains information such as variable references, variable counts, data offsets, sub-function codes etc
MODBUS Response PDU mb_rsp_pdu {function_code, response_data} function_code = [1 byte] MODBUS function code
response_data = [n bytes] This field is function code dependent and usually contains information such as variable references, variable counts, data offsets, sub-function codes, etc.
MODBUS Exception Response PDU mb_excep_rsp_pdu {exception-function_code, request_data} exception-function_code = [1 byte] MODBUS function code + 0x80
exception_code = [1 byte] MODBUS Exception Code Defined in table "MODBUS Exception Codes" (see section 7 ).

Data Encoding

MODBUS uses a ‘big-Endian’ representation for addresses and data items. This means that when a numerical quantity larger than a single byte is transmitted, the most significant byte is sent first. So for example :

Register size value
16 - bits 0x1234

the first byte sent is 0x12 then 0x34. By bitshifting and adding, the original value can be compiled. ( 0x12

MODBUS Data Model

MODBUS bases its data model on a series of tables that have distinguishing characteristics. The four primary tables are:

Primary tables Object type Type of Comments
Discretes Input Single Bit Read-Only This type of data can be provided by an I/O system.
Coils Single Bit Read-Write This type of data can be alterable by an application program.
Input Registers 16-bit word Read-Only This type of data can be provided by an I/O system
Holding Registers 16-bit word Read-Write This type of data can be alterable by an application program.

The distinctions between inputs and outputs, and between bit -addressable and word- addressable data items, do not imply any application behavior. It is perfectly acceptable, and very common, to regard all four tables as overlaying one another, if this is the most natural interpretation on the target machine in question. For each of the primary tables, the protocol allows individual selection of 65536 data items, and the operations of read or write of those items are designed to span multiple consecutive data items up to a data size limit which is dependent on the transaction function code. It’s obvious that all the data handled via MODBUS (bits, registers) must be located in device application memory. But physical address in memory should not be confused with data reference. The only requirement is to link data reference with physical address. MODBUS logical reference numbers, which are used in MODBUS funct ions, are unsigned integer indices starting at zero.

MODBUS Adressing Model

The MODBUS application protocol defines precisely PDU addressing rules. In a MODBUS PDU each data is addressed from 0 to 65535. It also defines clearly a MODBUS data model composed of 4 blocks that comprises several elements numbered from 1 to n. In the MODBUS data Model each element within a data block is numbered from 1 to n. Afterwards the MODBUS data model has to be bound to the device application ( IEC -61131 object, or other application model). The pre-mapping between the MODBUS data model and the device application is totally vendor device specific.

MODBUS Addressing Model

Define MODBUS Transaction

The following state diagram describes the generic processing oif a MODBUS transaction in server side.

MODBUS Transaction State Diagram

Once the request has been processed by a server, a MODBUS response using the adequate MODBUS server transaction is built. Depending on the result of the processing two types of response are built :

  • A positive MODBUS response :

    • the response function code = the request function code
  • A MODBUS Exception response ( see section 7 ):

    • the objective is to provide to the client relevant information concerning the error detected during the processing ;
    • the exception function code = the request function code + 0x80 ;
    • an exception code is provided to indicate the reason of the error.

Function Code Categories

There are three categories of MODBUS Functions codes. They are :

Public Function Codes

  • Are well defined function codes,
  • guaranteed to be unique,
  • validated by the MODBUS.org community,
  • publicly documented
  • have available conformance test,
  • includes both defined public assigned function codes as well as unassigned function codes reserved for future use.

User-Defined Function Codes

  • there are two ranges of user-defined function codes, i.e. 65 to 72 and from 100 to 110 decimal.
  • user can select and implement a function code that is not supported by the specification.
  • there is no guarantee that the use of the selected function code will be unique
  • if the user wants to re-position the functionality as a public function code, he must initiate an RFC to introduce the change into the public category and to have a new public function code assigned.
  • MODBUS Organization, Inc expressly reserves the right to develop the proposed RFC.

Reserved Function Codes

  • Function Codes currently used by some companies for legacy products and that are not available for public use.

Public Function Code Definition

Domain #Bits Type Description Function code Sub code (hex)
Data Access Bit Access Physical Discrete Inputs Read Discrete Inputs 02 0x02
Internal Bits or Physical Coils Read Coils 01 0x01
Write Single Coil 05 0x05
Write Multiple Coils 15 0x0F
16 bits access Physical Input Registers Read Input Register 04 0x04
Internal Registers or Physical Ouput Registers Read Holding Registers 03 0x03
Write Single Register 06 0x06
Write multiple Registers 16 0x10
Read/Write Multiple Registers 23 0x17
Mask Write Register 22 0x16
Read FIFO queue 24 0x18
File Record Access Read File record 20 0x14
Write File Record 21 0x15
Diagnostics Read Exception Status 07 0x07
Diagnostic 08 00-18,20 0x08
Get Com event counter 11 0x0B
Get Com Event Log 12 0x0C
Report Server ID 17 0x11
Read device Identification 43 14 0x2B
Other Encapsulated Interface Transport 43 13, 14 0x2B
CANopen General Reference 43 13 0x2B

Function codes descriptions

01 (0x01) Read Coils

This function code is used to read from 1 to 2000 contiguous status of coils in a remote device. The Request PDU specifies the starting address, i.e. the address of the first coil specified, and the number of coils. In the PDU Coils are addressed starting at zero. Therefore coils numbered 1-16 are addressed as 0-15.
The coils in the response message are packed as one coil per bit of the data field. Status is indicated as 1= ON and 0= OFF. The LSB of the first data byte contains the output addressed in the query. The other coils follow toward the high order end of this byte, and from low order to high order in subsequent bytes.
If the returned output quantity is not a multiple of eight, the remaining bits in the final data byte will be padded with zeros (toward the high order end of the byte). The Byte Count field specifies the quantity of complete bytes of data.

Request

Description #Bytes Value
Function code 1 Byte 0x01
Starting Address 2 Bytes 0x0000 to 0xFFFF
Quantity of coils 2 Bytes 1 to 2000 (0x7D0)

Response

Description #Bytes Value
Function code 1 Byte 0x01
Byte count 1 Byte N*
Coil Status n Byte n = N or N + 1

*N = Quantity of Outputs / 8, if the remainder is different of 0 => N = N+1

Error

Description #Bytes Value
Function Code 1 Byte Function code + 0x80
Exception Code 1 Byte 01, 02, 03 or 04

Here is an example of a request to read discrete output 20-38:

Request ++ Response ++
Field Name (Hex) Field Name (Hex)
Function 0x01 Function 0x01
Starting Address Hi 0x00 Byte Count 0x03
Starting Address Lo 0x13 Outputs status 27-20 0xCD
Quantity of Outputs Hi 0x00 Outputs status 25-28 0x6B
Quantity of Outputs Lo 0x13 Outputs status 38-36 0x05

The status of outputs 27–20 is shown as the byte value CD hex, or binary 1100 1101. Output 27 is the MSB of this byte, and output 20 is the LSB. By convention, bits within a byte are shown with the MSB to the left, and the LSB to the right. Thus the outputs in the first byte are ‘27 through 20’, from left to right. The next byte has outputs ‘35 through 28’, left to right. As the bits are transmitted serially, they flow from LSB to MSB: 20 . . . 27, 28 . . . 35, and so on. In the last data byte, the status of outputs 38-36 is shown as the byte value 05 hex, or binary 0000 0101. Output 38 is in the sixth bit position from the left, and output 36 is the LSB of this byte. The five remaining high order bits are zero filled.