modbus_read_registers(3) ======================== NAME ---- modbus_read_registers - read many registers SYNOPSIS -------- *int modbus_read_registers(modbus_t *'ctx', int 'addr', int 'nb', uint16_t *'dest');* DESCRIPTION ----------- The *modbus_read_registers()* function shall read the content of the _nb_ holding registers to the address _addr_ of the remote device. The result of reading is stored in _dest_ array as word values (16 bits). You must take care to allocate enough memory to store the results in _dest_ (at least _nb_ * sizeof(uint16_t)). The function uses the Modbus function code 0x03 (read holding registers). RETURN VALUE ------------ The function shall return the number of read registers if successful. Otherwise it shall return -1 and set errno. ERRORS ------ *EMBMDATA*:: Too many registers requested EXAMPLE ------- [source,c] ------------------- modbus_t *ctx; uint16_t tab_reg[64]; int rc; int i; ctx = modbus_new_tcp("127.0.0.1", 1502); if (modbus_connect(ctx) == -1) { fprintf(stderr, "Connection failed: %s\n", modbus_strerror(errno)); modbus_free(ctx); return -1; } rc = modbus_read_registers(ctx, 0, 10, tab_reg); if (rc == -1) { fprintf(stderr, "%s\n", modbus_strerror(errno)); return -1; } for (i=0; i < rc; i++) { printf("reg[%d]=%d (0x%X)\n", i, tab_reg[i], tab_reg[i]); } modbus_close(ctx); modbus_free(ctx); ------------------- SEE ALSO -------- linkmb:modbus_write_register[3] linkmb:modbus_write_registers[3] AUTHORS ------- The libmodbus documentation was written by Stéphane Raimbault